• Wide application range: multi-branch DC insulation monitor for DC systems up to 1500V, monitoring up to 30 branches. • Flexible monitoring methods: select the unbalanced bridge method for insulation resistance monitoring or the balanced bridge method for leakage current monitoring. • Comprehensive insulation monitoring: monitors the positive-to-ground and negative-to-ground resistance values of the entire system and of each branch, without being affected by the symmetry of positive and negative insulation resistance. • Continuous real-time monitoring: insulation resistance and leakage current values are updated in real time once the monitor is enabled. • Wide measurement range: total system insulation resistance up to 0KΩ ~ 10MΩ; branch insulation resistance up to 0KΩ ~ 2MΩ. • Adaptive ground capacitance: the larger the capacitance, the longer the monitoring cycle; the maximum cycle can be customized. • Easy installation and operation.


Empty
Download pdf add here
The GYDCG-MBC multi-branch DC insulation monitor checks the insulation of a DC system up to 1500VDC and of up to 30 individual branches at the same time. It consists of a main control module (GYDCG-MBC V1.0) and leakage current sensors (GYLCS), so a fault can be traced to the branch that causes it instead of only being reported for the whole system.
GYDCG-MBC Multi-Branch DC Insulation Monitoring System
The GYDCG-MBC Multi-Branch DC Insulation Monitoring System consists of a main control module (GYDCG-MBC V1.0) and multiple leakage current sensors (GYLCS).
The main control module is connected to the DC positive pole, negative pole, and ground. The positive and negative cables of each branch are connected in parallel through the leakage current sensors. The reference current direction marked on the sensor housing should match the cable current direction. The four control terminals of each leakage current sensor (G, M, -, +) are connected to the corresponding terminals (G, M, -, +) of the main control module channels B1~B30 to complete the system installation.
The B1~B30 ports of the main control module represent 1st to 30th branch channels. The leakage current sensors must be connected sequentially starting from B1.
A standard insulation monitor tells you that insulation has dropped somewhere on the DC bus. In a container or plant with many rack strings, the next question is which branch. With the GYDCG-MBC, each branch cable pair passes through a GYLCS leakage current sensor, and the main module reports the positive-to-ground and negative-to-ground resistance and the leakage current of every branch. The faulty branch can then be identified while the system keeps running, instead of disconnecting branches one by one. The principle is compared with other methods in our DC ground fault detection guide.
Up to 30 branches, on channels B1 to B30.
DC systems up to 1500VDC. Total system insulation resistance is monitored up to a range of 0KΩ ~ 10MΩ, and branch insulation resistance up to 0KΩ ~ 2MΩ.
You can select the unbalanced bridge method for insulation resistance monitoring or the balanced bridge method for leakage current monitoring.
The module adapts to ground capacitance automatically. The larger the capacitance, the longer the monitoring cycle, and the maximum cycle can be customized to customer requirements.
Gongyuan (Suzhou Gongyuan Automation Technology Co., Ltd.) has focused on insulation monitoring since 2017 and operates a quality management system built to the ISO 9001:2015 standard. For a multi-branch project, send the number of branches, DC voltage and communication needs through our contact page. Certificates and test reports are listed on the Certifications page. Specifications on this page come from Gongyuan’s product documentation; please confirm the final model and options with our engineers before ordering.