Dimensions



• High voltage application: 2000V DC insulation monitor designed for insulation resistance monitoring in DC systems up to 2000V. • Multi-function integration: integrates charging pile voltage measurement, insulation resistance monitoring and alarm output. • Power supply compatibility: compatible with 12V or 24V power supply. • Real-time insulation resistance monitoring. • Higher reliability: insulation resistance monitoring results remain unaffected under low-frequency DC voltage fluctuations. • Faster monitoring speed: adaptive ground capacitance matching for rapid insulation resistance monitoring. • Convenient parameter configuration: all communication parameters can be configured using DIP switches.


Empty
The GYDCG-UBCW2K 2000V DC insulation monitor monitors the insulation resistance between the positive and negative poles and ground in 100~2000VDC floating DC systems. It is a high-voltage DC insulation monitor with a 0KΩ~10MΩ measuring range, a dry contact relay alarm output and RS485 MODBUS RTU communication, used in EV charging systems, photovoltaic systems, energy storage systems and DC power grids.
GYDCG-UBCW2K Series High Voltage DC Insulation Monitor
GYDCG-UBCW2K series high-voltage DC insulation monitors can monitor the insulation resistance between the positive/negative poles and ground in real time after the module is powered on and insulation monitoring is enabled. The monitoring results are not affected by DC voltage fluctuations or the symmetry of positive and negative insulation resistance.
The GYDCG-UBCW2K-RS and GYDCG-UBCW2K-RSA models support module control and data reading through RS485 communication. After power-on, the insulation monitoring function is disabled by default.
The GYDCG-UBCW2K-A (without communication) and GYDCG-UBCW2K-ARS models enable insulation monitoring by default after power-on.
The UBCW2K is made for floating DC buses up to 2000Vdc, for example a 2000Vdc battery storage bus. On such a bus the first insulation fault gives no breaker trip and no visible symptom. The monitor tracks positive-to-ground and negative-to-ground insulation continuously and signals a fault through the relay output, so maintenance can be planned before a second fault creates a short circuit. For a worked example on a storage bus, read our BESS insulation monitoring guide.
100~2000VDC floating DC systems, with DC voltage detection from 0 to 2000VDC.
-RS and -RSA are controlled and read through RS485 and start with monitoring disabled. -A has no communication and -ARS has RS485; both start monitoring automatically after power-on.
All communication parameters can be set with DIP switches.
It is compatible with a 12V or 24V power supply.
Gongyuan (Suzhou Gongyuan Automation Technology Co., Ltd.) has focused on insulation monitoring since 2017 and operates a quality management system built to the ISO 9001:2015 standard. Send your DC bus voltage, the model variant you need and your application through our contact page for a recommendation. Certificates and test reports are listed on the Certifications page. Specifications on this page come from Gongyuan’s product documentation; please confirm the final model and options with our engineers before ordering.
Reviews
There are no reviews yet.