Insulation Monitoring Device for EV Chargers: IEC 61851-23 Requirements Explained

Insulation Monitoring Device for EV Chargers: IEC 61851-23 Requirements Explained

Yes, a DC fast charger needs an insulation monitoring device. Its DC output is isolated from earth, so an insulation monitoring device for an EV charger must check insulation resistance to protective earth (PE) before charging starts and keep monitoring during charging. If insulation is too low, the charger must not start or must stop. IEC 61851-23 defines these requirements.

This guide explains why DC chargers float from earth, what IEC 61851-23 asks for, how the pre-charge insulation check runs, what causes insulation faults, how single-gun and dual-gun chargers differ, and how to choose an IMD. It is the EV charging pillar of our insulation monitoring series.

Why do DC EV chargers float from earth?

A DC charger converts AC grid power into a high-voltage DC output, commonly 400 V to 1000 V and rising. Inside the charger, this output is isolated from earth: neither DC pole is connected to PE. It is an IT system.

The safety reason is simple. If a person touches one live pole, current has no return path through earth, so it stays small. The drawback is that the first insulation fault gives no warning, and a second fault could create a short circuit or shock path. An IMD makes the first fault visible. The general principle is explained in our guide to how an insulation monitoring device works.

What does IEC 61851-23 require for insulation monitoring?

IEC 61851-23 covers the safety and performance of DC EV charging stations. For insulation it expects the charger to:

  • Check insulation before charging and only close the output contactors to the vehicle if the result is acceptable.
  • Monitor insulation during charging and react if it deteriorates.
  • Report the result to the charger controller, and to the vehicle where the protocol requires it.

Limits are expressed in ohms per volt (Ω/V) of the DC output voltage. As a general summary of common practice, verify it against the edition you design to:

Insulation resistanceTypical result
Above 500 Ω/VInsulation OK, charging allowed
Between 100 Ω/V and 500 Ω/VWarning; charging may continue with monitoring, depending on the implementation
Below 100 Ω/VInsulation fault; charging must not start, or must stop

In China, GB/T 18487.1 and the GB/T 27930 communication protocol follow a similar approach. Exact clauses, limits and required responses differ between editions and protocols, so confirm them for your market. Two related standards are IEC 61557-8 (the IMD itself) and ISO 6469-3 (electrical safety on the vehicle side).

What do these limits mean in kΩ?

Multiply the Ω/V value by the DC output voltage.

Charger output voltageFault limit at 100 Ω/VOK level at 500 Ω/V
500 V50 kΩ250 kΩ
750 V75 kΩ375 kΩ
1000 V100 kΩ500 kΩ

Higher-voltage chargers therefore need an IMD that can measure accurately over a wider range.

How does the insulation check run before and during charging?

The sequence depends on the protocol (GB/T, CCS or CHAdeMO). A typical flow is:

  1. Connect and lock: The gun is plugged in and locked, and communication starts.
  2. Insulation test: The charger applies a test voltage to the DC output, and the IMD measures insulation resistance to PE.
  3. Decide: If the result is acceptable, the process continues. If not, the charger stops and reports an insulation fault.
  4. Discharge: The test voltage is discharged safely before the contactors close.
  5. Charge: The contactors close and the IMD keeps monitoring while the vehicle charges.
  6. Stop and discharge: At the end of the session the output is discharged again.

Drivers notice step 2 as a short delay after plugging in. An insulation failure or timeout at this stage is a common reason charging does not start.

What is the difference between the pre-charge check and monitoring during charging?

The two are often mixed up, but they do different jobs.

The pre-charge insulation check is an active test. The charger applies a test voltage, measures the result and decides whether it is safe to start. It happens once per session and protects the driver at the moment the contactors close.

Monitoring during charging is continuous. It watches for insulation that degrades while energy flows, for example because of a fault that develops in the vehicle or in the cable. It has to keep working while the charger output voltage and current change, so the IMD must handle a moving DC voltage.

A charger that only tests before charging leaves a gap for the rest of the session. That is why continuous monitoring is part of the requirement.

Where is the IMD connected in a DC charger?

The IMD is normally connected between the DC output of the charger and PE, on the output side of the power modules. From there it sees the power electronics, the internal DC wiring, the cable and, once the contactors are closed, the vehicle’s high-voltage system.

Two design points follow from this:

  • Contactor position matters: The IMD sees only the charger before the contactors close, and charger plus vehicle after. The controller must interpret the reading for the correct state.
  • One active monitor per isolated network: If the charger has several power modules on one DC bus, plan a single active measuring point so the devices do not disturb each other.

How does leakage capacitance affect the insulation check?

DC chargers contain EMC filters, Y-capacitors and long output cables, all of which add capacitance between the DC output and PE. The vehicle adds its own Y-capacitance when connected.

This capacitance has to charge to the measuring voltage, so a large value slows the measurement. If the IMD is not designed for it, the check may run into the protocol time limit and end as a timeout, or give an unstable reading. Chargers with long cables, high power or multiple modules are most exposed.

For this reason, ask the IMD supplier for the maximum leakage capacitance the device supports and check it against the real charger design.

What causes insulation faults in EV chargers?

SourceTypical causes
ChargerCondensation in the cabinet, faulty power module, ageing Y-capacitors, damaged internal wiring
Cable and gunCrushed or worn cable, moisture in the connector, dirty contacts
VehicleDamaged high-voltage cable, leaking battery pack, fault in an on-board component
MeasurementLarge leakage capacitance that slows or disturbs the measurement and causes false alarms

Because the fault can sit in the charger or the vehicle, the charger should report the result clearly and log every event. That helps the operator decide whether to service the charger or advise the driver.

How can operators troubleshoot “insulation detection failed” or “timeout”?

Operators searching for this problem usually see one of three messages. Use the table as a starting checklist.

MessageLikely causesWhat to check
Insulation detection failedReal low insulation in the charger, cable or vehicleTry another vehicle; inspect gun, cable and connector for moisture or damage; check the IMD reading in the charger
Insulation detection timeoutSlow measurement due to high leakage capacitance, or a communication delayCheck measurement settings and CAN/RS485 wiring; confirm the IMD suits the system capacitance
Insulation alarm during chargingInsulation dropped during the sessionLog the time, inspect the vehicle side, then the cable and gun after the session

If the fault follows one vehicle across chargers, the vehicle is likely the source. If it follows one charger across vehicles, service the charger.

Single-gun vs dual-gun chargers: how does monitoring differ?

A single-gun charger has one DC output and one monitored circuit.

A dual-gun charger has two outputs, which may share power modules and the same PE. Each output needs its own insulation check, and the measurement of one gun must not disturb the other. Shared measurement circuits can also make it harder to tell which gun caused the fault. Gongyuan’s UBCH1 and UBCH2 models are designed for dual-gun charger layouts. [[Add the product page link and confirm channel count and specifications with the product team.]]

CAN or RS485: how does the IMD talk to the charger controller?

InterfaceTypical use
CANReal-time communication, common in charger controllers
RS485 (Modbus)Simple, robust and widely supported

Choose the interface your controller already uses, and confirm the update rate is fast enough for the pre-charge test window.

How do you choose an IMD for an EV charger?

  1. Voltage range: The IMD must be rated above the maximum DC output voltage, with margin.
  2. Measuring range and accuracy: It must measure the Ω/V limits at your voltage.
  3. Response time: The pre-charge check has a limited window.
  4. Number of outputs: Single-gun or dual-gun.
  5. Communication: CAN or RS485, to match the controller.
  6. Standards and certificates: Look for IEC 61557-8 conformity and certification for your target market.
  7. Size and installation: Space inside a compact charger is limited.
  8. Tolerance of leakage capacitance: The device should stay stable with large Y-capacitance.

Which Gongyuan IMD fits which charger voltage?

Charger applicationSuggested Gongyuan model
Up to 2000 VdcUBCW2K
Up to 4000 VdcUBCW4K
Dual-gun chargersUBCH1 / UBCH2

Chargers that include local energy storage also need monitoring on the battery bus. See insulation monitoring for battery energy storage systems. For integration examples, see our application case on charging pile integration.

What should charger manufacturers check before shipping?

Use this list during factory acceptance testing:

  1. Insulation check works on both polarities, at rated output voltage.
  2. Simulated fault using a calibrated resistor to PE shows the correct warning and fault states.
  3. Timing: The check finishes within the protocol time limit, even with maximum cable capacitance.
  4. Communication: The controller receives the value and alarm state over CAN or RS485.
  5. Logging: Each insulation event is stored with a time stamp.
  6. Dual-gun independence: A fault on one gun does not affect the other gun’s result.
  7. Documentation: Settings and test results are recorded for the certification file.

Frequently asked questions

Why do DC EV chargers need an insulation monitoring device?

The DC output is ungrounded, so the first insulation fault gives no warning. The IMD detects it before a second fault creates a short circuit or shock hazard.

What does IEC 61851-23 say about insulation?

It calls for an insulation check before charging and monitoring during charging, with limits in Ω/V. The charger must not charge, or must stop, if insulation is too low.

Why does my charger say “insulation detection failed”?

Common causes are moisture in the connector, damaged cable insulation, a vehicle-side fault or slow measurement caused by leakage capacitance. Check the gun and cable first, then the charger.

Do dual-gun chargers need two IMDs?

Each output needs its own insulation measurement. That can be one multi-channel device or separate devices, depending on the design.

What voltage rating should the IMD have?

It must exceed the maximum charger output voltage with a safety margin. Choose the 1000, 2000 or 4000 Vdc class to suit the charger.

Does the charger’s IMD replace the vehicle’s own isolation monitoring?

No. The vehicle monitors its own high-voltage system. The charger monitors its DC output and the cable. Both are needed.

Conclusion

A DC EV charger runs an ungrounded high-voltage output, so it needs an insulation monitoring device for the pre-charge check and for monitoring during charging. IEC 61851-23 sets the requirement, and the right IMD depends on voltage, number of guns and controller interface.

Need an IMD for your charger design? Contact Gongyuan’s engineers with your charger voltage, number of guns and communication interface, and we will recommend a model.

For an overview of the DC EV charging safety framework, see the IEC 61851 page on Wikipedia.